Data center cooling can actually reduce water demand, but the outcome depends on how heat leaves the facility. Comparing air cooling, direct-to-chip systems, and outdoor heat rejection shows why engineering professionals must assess electricity, water, and reliability together.
A data center’s water footprint can be decided well beyond its server racks. Water circulating through a processor’s cooling loop may be reused repeatedly, while an outdoor cooling tower consumes water through evaporation.
These process differences sits behind the question of whether more computing power must mean more cooling water. Berkeley Lab’s overview of data center research describes work spanning liquid-cooled supercomputers, operating improvements, and simulation tools that consider energy use and reliability. For engineering professionals, the task is to evaluate the complete cooling system.
Air or Liquid: How Computers Lose Heat
Air cooling works on a familiar principle. Much like a laptop fan, fans inside a server move air across hot parts and carry heat away. The warmed air then needs to be cooled or removed.
Keeping hot exhaust air separate from the cooler air entering the computers helps the system work more efficiently.
Direct-to-chip liquid cooling takes a different approach. Metal plates sit against heat-producing parts, such as processors. Liquid flows through channels inside those plates and carries the heat away. The liquid stays inside the cooling equipment; it is not poured over the electronics.
This can help cool powerful computers without moving as much air around the room. Some parts may still need fans, depending on the equipment.
As the US Department of Energy’s design guide explains, both approaches are part of a larger system. Calling a computer “air-cooled” or “liquid-cooled” does not, by itself, tell us how much water the whole facility uses.
Where the Heat Goes Matters
Once heat has been collected, the facility needs somewhere to release it. This is where much of the water question is decided.
Dry coolers pass outdoor air over pipes containing warm liquid. Heat moves into the air while the liquid stays inside the pipes. This avoids using evaporation for cooling. However, releasing heat becomes harder when the outdoor air is already hot.
Cooling towers use evaporation to remove heat. Think of how evaporation helps cool your skin when you sweat. This can be an efficient way to carry heat away, but the evaporated water must be replaced. Some water is also drained to control the buildup of dissolved minerals.
Air-cooled chillers use refrigeration, similar in principle to an air conditioner, and release heat into outdoor air. They avoid a cooling tower’s evaporative water demand, but their electricity use and performance still need checking during hot weather.
Hybrid systems combine these approaches. They can use dry cooling when the weather allows and bring in water-assisted cooling when more help is needed.
The 2024 US Data Center Energy Usage Report describes these different combinations.
The distinction is important: liquid can circulate through a computer’s cooling loop repeatedly, while a cooling tower elsewhere on the site continues to use water.
A Real Example of Water Savings
A Department of Energy case study describes how the National Renewable Energy Laboratory added a dry cooling device to a system that already used cooling towers.
The addition roughly halved the data center’s water use while maintaining energy efficiency. It allowed more heat to be released without evaporating water when outdoor conditions were suitable.
The towers still needed enough capacity for the hottest weather. For engineering professionals, that means checking both the savings over a year and what the system needs on its most demanding days.
Compare Electricity and Water Together
A system that uses less water may need more electricity. Another may use less electricity while relying more heavily on evaporation.
Engineering professionals need to compare both, using the same amount of computing work and the same weather conditions.
Two common measures help. Power usage effectiveness (PUE) compares the electricity used by the whole facility with the electricity used by its computers. It helps show the extra power needed for cooling and other support equipment.
Water usage effectiveness (WUE) describes how much water the site uses for each unit of electricity used by its computers. The Federal Energy Management Program explains both measures.
These figures should sit alongside actual electricity and water totals. Engineering professionals also need to distinguish water taken into the site from water consumed through evaporation.
There is another connection to consider: generating electricity can itself consume water. Berkeley Lab’s report shows that this varies by location and electricity source. Saving water at the data center therefore needs to be considered alongside any increase in power demand.
Keep Computers Running When Conditions Change
Efficiency also depends on whether the cooling system can keep working through problems.
A useful assessment asks:
- Can it keep the computers cool during a heatwave?
- What happens if the water supply is restricted?
- If a pump or fan stops, can backup equipment take over in time?
- Can a leak be detected and the affected section isolated?
- Can equipment be serviced while the rest of the facility stays cool?
The Open Compute Project’s liquid-cooling guidance addresses monitoring and leak detection, among other requirements.
Engineering professionals should also check what backup equipment shares. Two pumps connected to the same failed power supply, for example, may both stop working.
Choose Cooling That Fits the Location
Data centers can reduce their cooling water demand. The best approach depends on the local climate, available water, computer equipment, and the level of reliability the facility needs.
A cooler location may offer more opportunities to release heat directly into outdoor air. A hotter location may need additional cooling for its most demanding days. Where water supplies are limited, reducing dependence on evaporation becomes especially important.
Engineering decisions therefore need to answer three questions together: How much electricity will the system use? How much water will it need? And will it keep the computers cool when conditions become difficult?
These decisions draw on heat transfer and fluid engineering, subjects covered in the Engineering Institute of Technology’s (EIT) Master of Engineering (Mechanical).
References
Lawrence Berkeley National Laboratory. How Researchers Are Driving Advances for Data Centers. December 16, 2025.
US Department of Energy / Lawrence Berkeley National Laboratory. Best Practices Guide for Energy-Efficient Data Center Design. Revised July 2024.
US Department of Energy, Federal Energy Management Program. Cooling Water Efficiency Opportunities for Federal Data Centers. January 9, 2019.
US Department of Energy. Using Thermosyphon Hybrid Cooling System to Optimize Data Center Water Efficiency. May 2019.
Lawrence Berkeley National Laboratory. 2024 United States Data Center Energy Usage Report. December 2024.
Open Compute Project. Liquid Cooling Cold Plate Requirements Document.
This article was published November 16th, 2026 and the content is current as at the date of publication.